I. Overview

TC-803 series input level transmitter has small structure, fast response and high measurement accuracy. It is widely used in metallurgy, petroleum, chemical, water conservancy, medicine , food, power environment control and liquid level measurement. In addition, this product has a live indication function that allows easy and intuitive reading of the actual measured level.

Second, the working principle

Static pressure measurement principle: When the liquid level transmitter is put into the liquid, the pressure on the liquid-facing surface of the sensor is P=ρ·g·h+P0

In the formula

P: Pressure on the liquid surface of the sensor Unit: Pa

ρ: measured liquid density unit: Kg/m3

g: local gravity acceleration unit: m/S2

P0: Atmospheric pressure on the liquid level Unit: Pa

h: sensor input liquid depth unit: m

The atmospheric pressure P0 on the liquid surface can be led to the back pressure chamber of the sensor through the air guiding cable to eliminate the P0 of the liquid surface of the sensor, and the measured pressure is P=·g·h, so as long as the pressure P is measured, The liquid level depth H is available. The pressure signal sensed by the sensor is amplified by circuit conversion and outputted with a standard 4-20 mA·DC signal after compensation. This product is suitable for measuring the liquid level of the open container.

Third, product features

● Good stability, high precision and high cost performance;

● Directly put into the measured medium, it is very convenient to install and use;

● Solid structure, no moving parts, high reliability and long service life;

● The paste with high viscosity from water to oil can be measured with high precision, without being affected by foaming, deposition and electrical properties of the measured medium;

● No material fatigue wear, not sensitive to vibration and impact;

● 4-20mA·DC output (optional HART protocol);

● With lightning protection;

Fourth, technical parameters

Measuring range: 0.5 ~ 200m;

Accuracy: ±0.25% FS, ±0.5% FS

Power supply: 24V·DC (15~36V·DC);

Output signal: 4-20mA·DC two-wire system (with HART protocol);

Load capacity: 600Ω (24V·DC);

Working pressure: atmospheric pressure (through the atmosphere);

Working temperature: -20 ~ 185 ° C, ambient temperature: -30 ~ 80 ° C;

Environmental temperature effect: Zero variation in temperature compensation range ≤ ± 0.2% FS;

Installation method: bracket, thread, flange installation;

Electrical interface: 2 M20 × 1.5 internal threads;

Protection level: Explosion-proof ExdIIBT4~T6; Intrinsic safety type: ExiaIICT4~T6;

Protection level: IP65

Wetted material: cable type: stainless steel, PVC or oil resistant rubber, fluoro rubber;

Rod type: stainless steel, fluoro rubber


V. Selection table


Inquiry

Customer Service Hotline:13938765366

Company Telephone:13938765366

公司传真:0755-66803070

Office Mailbox:Tianchenyb@163.com

Company Address:North Section of Yuanxin Road, Xinxiang City, Henan Province

Mobile

  • Scanning ConcernsHenan Tianchen Measurement and Control Instrument Co., Ltd.

  • 扫描关注共赢国际